top image

Mobile Power Distribution Boxes of Solid Rubber – Floor-Mounted –

Solid Rubber Safety Distribution Boxes Series HAMBURG

vollgummi-sicherheitsverteiler-baureihe-hamburgicon

Mobile Power Distribution Boxes of Solid Rubber – Floor-Mounted –

Solid Rubber Safety Distribution Boxes Series HAMBURG

icon

General

Please regard the basic models shown on this page as examples which can be modified to meet your demands.

The XXL Distribution Box

The stable base frame and the generous clearance are just two of the many outstanding features that distinguish the HAMBURG distribution box. Additionally, more than one connection housing can be installed under the distribution box (see fig.). This significantly enhances the technical possibilities. 5.150 cm2 of area are available for individual configurations and serve to facilitate the implementation of complex application profiles. Frame design is adaptable to individual demands, including a trolley version. These features make HAMBURG the No. 1 XXL series among mobile power distributors.

  • Design
  • Input
  • Output
  • K2 accomplishment
  • shockproof and splashproof
  • protection devices are externally accessible behind 6 transparent hinged windows
  • the distributing box is assembled to a galvanised and stable tubular frame, which allows a fork lift transport
  • a full-loaded terminal block to connect feeders
  • K2 accomplishment
  • shockproof and splashproof
  • protection devices are externally accessible behind 6 transparent hinged windows
  • the distributing box is assembled to a galvanised and stable tubular frame, which allows a fork lift transport
  • a full-loaded terminal block to connect feeders
  • 2 rubber cable entries with 1 high current terminal block for looping the feed line, max. 2x5x70 mm² (max. pre-fuse protection 125 A), with external traction load rejection
  • 2 rubber cable entries with 1 high current terminal block for looping the feed line, max. 2x5x70 mm² (max. pre-fuse protection 125 A), with external traction load rejection
  • 2 CEE built-in sockets 5×63 A/400 V fused over 2 MCB 63 A/3 pol. in C-characteristic as well as over each RCD 63 A/30 mA/4 pol. single leaded
  • 4 CEE built-in sockets 5×32 A/400 V fused over 4 MCB 32 A/3 pol. in C-characteristic
  • 4 CEE built-in sockets 5×16 A/400 V fused over 4 MCB 16 A/3 pol. in C-characteristic
  • 12 shockproof sockets fused over 12 MCB 16 A/1 pol. in B-characteristic
  • each with 2xCEE 32 A, 2xCEE 16 A and 6 shockproof sockets are leaded over each RCD 63 A/30 mA/4 pol, which are prefused over MCB 63 A/3 pol.
  • Additional installation: 1 main switch 125 A/3 pol. for general shutdown
  • 2 CEE built-in sockets 5×63 A/400 V fused over 2 MCB 63 A/3 pol. in C-characteristic as well as over each RCD 63 A/30 mA/4 pol. single leaded
  • 4 CEE built-in sockets 5×32 A/400 V fused over 4 MCB 32 A/3 pol. in C-characteristic
  • 4 CEE built-in sockets 5×16 A/400 V fused over 4 MCB 16 A/3 pol. in C-characteristic
  • 12 shockproof sockets fused over 12 MCB 16 A/1 pol. in B-characteristic
  • each with 2xCEE 32 A, 2xCEE 16 A and 6 shockproof sockets are leaded over each RCD 63 A/30 mA/4 pol, which are prefused over MCB 63 A/3 pol.
  • Additional installation: 1 main switch 125 A/3 pol. for general shutdown