Input: |
| |
20 m cable INDUSTRIEFLEX07 5x16 mm²
with CEE-plug 5x63 A/400 V |
 |
on lateral cable take-up |
| |
|
 |
Installations: |
| 1 |
Main switch 63 A/3 pol.
for total circuit breaking |
| |
|
 |
Transformers: |
| 1 |
Isolating transformer
Rated power: 4.500 VA
Rated voltage: 3x400 V/3x400 V
Rated frequency: 50 - 60 Hz
Switches: Dyn 5 |
 |
primary fused over a
motor-circuit switch 4 - 6 A/ 3pol. |
| |
|
 |
Output: |
| 1 |
CEE built-in socket 5x16 A/400 V |
| 4 |
Isolating transformers, each
Rated power: 2.500 VA
Rated voltage: 230 V/230 V
Rated frequency: 50 - 60 Hz |
 |
primary fused by each over a
thermal overcurrent circuit breaker |
| |
|
 |
Output: |
| 4 |
shock proof sockets
(without earthing contact) |
| 1 |
Safety isolating transformer
Rated power: 5.500 VA
Rated current: 3x400 V/3x42 V
Rated frequency: 50 - 60 Hz
Switches: Dyn 5
|
 |
primary fused by over a
motor-circuit switch 6-10 A/3 pol.
- preset to 7,9 A – |
| |
|
 |
Output: |
| 6 |
CEE built-in sockets 3x32 A/42 V
fused over neozed-
fuses 32 A/3 pol. |
| |
|
 |
Ventilation: |
| 2 |
Axial fan,
single fused by neozed-fuses |
| 2 |
filtered ventilation grids |
| |
|
 |
Design: |
| |
- built in a completely all-insulated design
- splashproof
- steel frame revision-dare is protected by a plastic flux coating
- with 2 full rubber support swivel rollers and
2 full rubber swivel rollers (wheel diameter = 200 mm),
all with parking brake
- ramming protection above and down
- cover plate with structured mat as tool shelf,
to be easily taken off after after removing the
4 crane eyes
- the protection devices are located in the switchgear cabinet
behind a door which is lockable with 2 sash fasteners |
| |
|
 |
Special features: |
 |
the box consists of impact resistant hostalit, cover plate
15 mm, side parts 10 mm |
 |
resistant against acid and caustic solutions |
 |
high mechanical solidity |
 |
of low flammability as per DIN 4102, B1 |
 |
sockets with nickel plated contacts,
individually replaceable, VDE-examided and approved |
 |
adherance to all technical regulations and all valid electrotechnical
safety regulations of VDE
|
| |
|