Please regard the basic models shown on this page as examples which
can be modified to meet your demands.
For detailed information download our data sheet.
For
your convenience we provide a contact
form for your inquiries!
Example (large image)
Input:
2
rubber cable entries with
1 high current terminal block for looping the
feed line, max. 2x5x70 mm²
(max. pre-fuse protection 125 A),
with external traction load rejection
Output:
2
CEE built-in sockets 5x63 A/400 V
fused over 2 MCB
63 A/3 pol. in C-characteristic
as well as over each
RCD 63 A/30 mA/4 pol. single leaded
4
CEE built-in sockets 5x32 A/400 V
fused over 4 MCB
32 A/3 pol. in C-characteristic
4
CEE built-in sockets 5x16 A/400 V
fused over 4 MCB
16 A/3 pol. in C-characteristic
12
shockproof sockets
fused over 12 MCB
16 A/1 pol. in B-characteristic
each with 2xCEE 32 A, 2xCEE 16 A
and 6 shockproof sockets
are leaded over each
RCD 63 A/30 mA/4 pol,
which are prefused over MCB 63 A/3 pol.
Additional installation:
1
main switch 125 A/3 pol.
for general shutdown
Design:
- K2 accomplishment
- shockproof and splashproof
- protection devices are externally accessible
behind 6 transparent hinged windows
- the distributing box is assembled to a galvanised and
stable tubular frame, which allows a fork lift transport
- a full-loaded terminal block to connect feeders